How to Read Allen-Bradley Tags Without RSLinx

You do not need RSLinx, FactoryTalk Linx or an OPC server just to read a ControlLogix or CompactLogix tag. The controller answers tag reads over EtherNet/IP itself. Here is what to enter and what to check when it fails.

Updated · Gixtronix Technologies

Why RSLinx is not required

ControlLogix and CompactLogix controllers speak CIP over EtherNet/IP on TCP port 44818, and CIP lets a client read a tag directly by its name. RSLinx Classic and FactoryTalk Linx are Rockwell's communication servers for Rockwell software and for OPC clients. A tool with its own CIP driver, such as SignalStream Studio, talks to the controller directly, with no Rockwell software on the PC.

This applies to tag-based Logix controllers. PLC-5, SLC 500 and MicroLogix use file addresses like N7:0 and need a different driver.

What you need

  • The controller's IP address (or its Ethernet module's), reachable from the PC.
  • TCP port 44818 open between the PC and the controller.
  • The tag names, exactly as they appear in Studio 5000 Logix Designer.
  • External Access on each tag set to Read/Write or Read Only, not None.

The path: IP address and slot

Where the controller sits decides what you enter as the address:

HardwareWhat to enterExample
CompactLogix with built-in EthernetThe controller's IP address192.168.1.20
ControlLogix, controller in slot 0The Ethernet module's IP address192.168.1.30
ControlLogix, controller in another slotEthernet module IP, a slash, the controller's slot192.168.1.30/2

In a ControlLogix chassis you connect to the Ethernet module (such as a 1756-EN2T), and the slot tells it which backplane slot holds the controller.

Writing tag names

Tag kindHow to write itExample
Controller-scopedJust the nameTank_Level
Program-scopedProgram:, the program name, a dot, the tagProgram:MainProgram.Tank_Level
UDT memberTag, a dot, the memberLine1.Speed
Array elementTag with an indexCounts[3]

Logix tag names are not case-sensitive, but spelling and the program name must match exactly. Read whole UDTs and arrays member by member.

When the read fails

  • Cannot connect: the IP is wrong, port 44818 is blocked by a firewall, or the PC is on a different subnet with no route.
  • Connects but the tag is not found: check spelling, and add Program:Name. for program-scoped tags.
  • Connects, the tag exists but cannot be read: its External Access is None. Change it in the tag's properties in Studio 5000.
  • Errors on a ControlLogix only: the slot after the slash is missing or points at the wrong module.

Reading it in SignalStream Studio

In Studio's EtherNet/IP wizard, enter the address (with /slot if needed) and the tag name. Test Poll reads the tag live and shows the controller's own error if something is wrong. BOOL, integer, REAL and STRING tags come through as values; Studio only reads, so it never changes a running controller.

Frequently asked questions

Do I need RSLinx to read tags from a CompactLogix?

No. CompactLogix and ControlLogix answer tag reads over EtherNet/IP directly. RSLinx or FactoryTalk Linx is only needed by software that relies on it, such as Rockwell's own tools or an OPC client.

What port does EtherNet/IP use?

TCP 44818 for explicit messaging such as tag reads. UDP 2222 carries I/O traffic, which tag reads do not use.

How do I read a program-scoped tag?

Prefix it with Program: and the program name: Program:MainProgram.MyTag.

Why can I see a tag in Studio 5000 but not read it?

Usually its External Access is set to None, which blocks every external client. Set it to Read Only or Read/Write.

Does this work with MicroLogix or SLC 500?

Not with a tag-based driver. Those controllers use file addresses such as N7:0. SignalStream Studio supports ControlLogix and CompactLogix.