Why RSLinx is not required
ControlLogix and CompactLogix controllers speak CIP over EtherNet/IP on TCP port 44818, and CIP lets a client read a tag directly by its name. RSLinx Classic and FactoryTalk Linx are Rockwell's communication servers for Rockwell software and for OPC clients. A tool with its own CIP driver, such as SignalStream Studio, talks to the controller directly, with no Rockwell software on the PC.
This applies to tag-based Logix controllers. PLC-5, SLC 500 and MicroLogix use file addresses like N7:0 and need a different driver.
What you need
- The controller's IP address (or its Ethernet module's), reachable from the PC.
- TCP port 44818 open between the PC and the controller.
- The tag names, exactly as they appear in Studio 5000 Logix Designer.
- External Access on each tag set to Read/Write or Read Only, not None.
The path: IP address and slot
Where the controller sits decides what you enter as the address:
| Hardware | What to enter | Example |
|---|---|---|
| CompactLogix with built-in Ethernet | The controller's IP address | 192.168.1.20 |
| ControlLogix, controller in slot 0 | The Ethernet module's IP address | 192.168.1.30 |
| ControlLogix, controller in another slot | Ethernet module IP, a slash, the controller's slot | 192.168.1.30/2 |
In a ControlLogix chassis you connect to the Ethernet module (such as a 1756-EN2T), and the slot tells it which backplane slot holds the controller.
Writing tag names
| Tag kind | How to write it | Example |
|---|---|---|
| Controller-scoped | Just the name | Tank_Level |
| Program-scoped | Program:, the program name, a dot, the tag | Program:MainProgram.Tank_Level |
| UDT member | Tag, a dot, the member | Line1.Speed |
| Array element | Tag with an index | Counts[3] |
Logix tag names are not case-sensitive, but spelling and the program name must match exactly. Read whole UDTs and arrays member by member.
When the read fails
- Cannot connect: the IP is wrong, port 44818 is blocked by a firewall, or the PC is on a different subnet with no route.
- Connects but the tag is not found: check spelling, and add Program:Name. for program-scoped tags.
- Connects, the tag exists but cannot be read: its External Access is None. Change it in the tag's properties in Studio 5000.
- Errors on a ControlLogix only: the slot after the slash is missing or points at the wrong module.
Reading it in SignalStream Studio
In Studio's EtherNet/IP wizard, enter the address (with /slot if needed) and the tag name. Test Poll reads the tag live and shows the controller's own error if something is wrong. BOOL, integer, REAL and STRING tags come through as values; Studio only reads, so it never changes a running controller.